ATHENA CONTROLS, INC.5145 Campus DrivePlymouth MeetingPA 19462 U.S.A.Tel: (610) 828-2490Fax: (610) 828-7084AthenaControls.comControllerIndicator Trans
92 - Electrical connectionsPRECAUTIONSBDespite the fact that the instrumenthas been designed to work in anharsh and noisy environmental(level IV of th
102 - Electrical connections2.3 TYPICAL INSTRUMENT WIRINGB6V~SupervisorySupply V~V~Retransmission4…20mALNDC voltageThermocoupleCurrent2.5 Ω externals
112 - Electrical connections2.3.1 POWER SUPPLY BSwitching power supply with mul-tiple isolation and internal fuse• Standard version:nominal voltage:1
122 - Electrical connections2.3.4 PV CONTROL INPUTB• Connect the wires with thepolarity as shown• Use always compensation cableof the correct type fo
132 - Electrical connections2.3.5 OP4 OUTPUT (option)B2.3.6 SERIAL COMMUNICATIONS (option)BPV retransmission• Galvanic isolation500V~/1 min.• 0/4...
143 - Product coding3 PRODUCT CODINGThe complete code is shown onthe instrument label. The informa-tions about product coding areaccessible from the f
153 - Product codingOption 1 DOption 2Not provided0Not provided6Transmitter Power Supply (PS)RS485 Modbus/Jbus protocol0Not provided6Transmitter Power
163 - Product coding3.2 CONFIGURATION CODINGThe configuration code consists of4 digits that identify the operat-ing characteristic of the controller,
173 - Product codingAIf, when the controller is pow-ered up for the first time, the dis-play shows the following mes-sageit means that the controller
184 - Operations4 OPERATIONS4.1 KEYPAD COMMANDS AND DISPLAYValuesmodificationEnter key forselection andvalue settingconfirmationMenuaccessOP1 output
ControllerIndicator Transmitter 1/32DIN - 48 x 24 C10 line cc274.8ULCUSLISTED
194 - Operations4.2 DISPLAYWhen the display operation isselected, the controller presentsautomatically all the most impor-tant parameters and configu
204 - OperationsOperatormodeCurrent setpoint displaySetpoint modificationSetpoint entry.The operation isacknowledged byone flash of thedisplay.274.827
214 - OperationsEngineering UnitsDegree CentigradeDegree Fahrenheitno unitsdefinedDegree FahrenheitPh Unit °C °fnone °f ph4.3.2 MNEMONIC CODES SE
224 - Operations4.4 PARAMETER SETTINGAThe parameter setting procedurehas a timeout. If no keys arepressed for, at least, 30 seconds,the controller sw
234 - Operationsrt.Hihy.O.C.Op. Hsl. usl. ds.p. ls.p. HAIhytunet.filIn.shAddrrt.lopassA2hyP 1:00P100:0P 0:5P 0:5P 0:5P OffP OffPIn.sPcalaP OffP 0
244 - Operations4.5 PARAMETER 1st GROUPThe controller parameters havebeen organized in group, accord-ing to their functionality area.AL1 alarm thresho
254 - Operationseffectiveness of the PID algorithm.Setting 1, the overshoot control isdisabled.Control outputhigh limitIt specifies the maximum value
264 - Operations4.6 CONFIGURATIONThe configuration of the controlleris specified through a 4 digit codethat defines the type of input, ofcontrol outp
274 - OperationsNotePressing the Q the next group ofparameters is displayed.[1] Table of the supported EngineeringUnits.* For inputs from thermocouple
285 - Automatic tune5 AUTOMATIC TUNEStart/stop of the Fuzzy TuningThe Tuning operation can bestarted or stopped any time.The green led 3 goes on when
2informationccNOTESON ELECTRICSAFETY ANDELECTROMAGNETICCOMPATIBILITY.Please, read carefully these instructions before proceeding withthe installation
296 - Technical specification6 TECHNICAL SPECIFICATIONSCommon characteristicsA/D converter with resolution of 50.000 pointsUpdate measurement time: 0.
306 - Technical specificationFeatures(at 25°C enviromental temp.)Operating mode and OutputsControl ModeOP1 outputOP2 outputAL1 alarm (indicator with 2
Approvals316 - Technical specificationFeatures(at 25°C enviromental temp.)SetpointOP4 PV retransmission(option)One shot Fuzzy-Tuningwith automatic sel
32warranty1 WARRANTYWe warrant that the prod-ucts will be free fromdefects in material andworkmanship for 3 yearsfrom the date of delivery.The warrant
33Main universal input Digital inputThermocouple Isolated contactRTD (Pt100) NPN open collectorDelta Temp (2x RTD) TTL open collectormA and mVSetpoint
3Table of contentsTABLE OF CONTENTS 1 INSTALLATION...
41 - Installation1 INSTALLATIONInstallation must only be carriedout by qualified personnel.Before proceeding with the instal-lation of this controller
51 - Installation1.2 DIMENSIONAL DETAILS48 mm1.89 in25 mm0.99 in120 mm4.72 in20 mm max0.79 in max1.3 PANEL CUT-OUT65 mm min2.56 in min42 mm min.1.6
61 - InstallationSpecial conditionsMAltitude > 2000 mTTemperature >50°C%RhHumidity > 95 %PConducting atmosphereUse filterWarm upUse forced ai
71 - Installation1.5.1 INSERT THE INSTRUMENT1 Prepare panel cut-out2 Check front panel gasket posi-tion3 Insert the instrument through the cut-out1.5
82 - Electrical connections2 ELECTRICALCONNECTIONS2.1 TERMINATION UNITB12 screw terminalsOption terminalsHolding screw 0.5 NmPositive screw driver PH