15
Example: Error code in response to the request indicated above.
ADDR
FUNC
DATA
Except.
Code
CRC
HI
CRC
LO
0A 81 02 B0 53
4.1 Error Codes
Although the MODBUS standard uses 8 error codes, the ATHENA
CONTROLS implementation of the protocol uses only four:
Code Name Meaning
01
ILLEGAL FUNCTION
The function code received does not correspond
to a function allowed on the addressed slave.
02
ILLEGAL DATA
ADDRESS
The address to which the data field refers is not
an address allowed on the addressed slave.
03
ILLEGAL DATA VALUE
The value to be assigned, specified in the data
field, is not allowed for this address.
07
NAK - NEGATIVE
ACKNOWLEDGMENT
The function cannot be performed under the
current operating conditions or an attempt has
been made to write in a read-only address.
5. MODBUS ON ATHENA CONTROLS PLATINUM® INSTRUMENTS
5.1 Serial communications parameters
The parameters are shown in the below table:
Parameter Parameter
code
Set up range
Communications protocol
Prot MbuS / JbuS
Serial address
Addr 1 ... 247
Baud rate
baudr 1200, 2400, 4800, 9600, 19200
The protocol is chosen by means the M.buS o JbuS selection.
The address can be set among 1..247 and must be unique for each
instrument connected on the same line.
The Baud rate parameter enable a clear and simple communications
speed setting.
No Parity and stop bit must be set. They have already been set by the
manufacturer as follows:
Parity = none
Stop bit = 1
5.2 Communications time
The messages, as described in Chapter 2.4, must be exchanged with an
internal pause that is less than 3 times the time required for a character
to be exchanged, otherwise it would be interpreted as the end of the
message. The ATHENA CONTROLS instruments with the MODBUS
protocol are able to receive and transmit characters without an interval.
Between a master message and the following reply on the part of the
instrument there is a latent time lapse necessary for the completion of the
function. This is connected to the fact that, once a command has been
received, the instrument responds only after having completed the
Vista de página 14