5.6 Assignment of the parameters and E
2
PROM
All the parameters modified from keyboard or assigned through serial
communication, come written in a permanent way in the EEPROM of the
instruments. Like known good, these components have limited writing
cycles beyond to which the component could be damaged. In our case
the number of cycles of writing are about 10.000 and also if this number
could appear limited, we must be held present that the writings during the
arc of life of the instrument don't arrive to overcome the thousand of
cycles. Different thing is when we talk about the serial communication. In
fact the computer could assign any parameter and with any frequency to
the regulators.
Being well aware of this fact, Athena Controls has provided to protect the
component in matter according to different hardware formality and
resources of the instruments. One of the protection made consists of the
fact to compare the new given with the datum already resident. If the two
data correspond, no writing doesn't happen in as not necessary and the
new given comes writing only and entirely if the two data disagree
between them.
Normally the datum that has a frequency of better writing it is the value of
Setpoint. In the instruments C10, M10 and M300 in as not furnished of
NOVRAM or buffered RAM, exists two formality of assignment of the
Setpoint that is:
1) Assignment to the Jbus address 2
2) Assignment to the Jbus address 5
With the first formality, the Setpoint could be assigned endless times
because it work in the RAM of the microprocessor but attention because
at the turning off of the regulator this datum comes lost for engage the
last value that had stayed written locally from keyboard or from the serial
to the Jbus address 5.
With the second formality the datum comes written in a permanent way
directly in the EEPROM of the instrument and the writing must be limited
to a real necessity.
The instruments of the series M5000, X100, X400, X5000 and X7000
possessing a different hardware structure, furnished that is of NOVRAM
or buffered RAM, they are not subdued to the limits previously exposed
and the assignments of the Setpoint to the Jbus addresses 2 or 5 don't
involve any difference. The two addresses come maintained active only
for a problem of compatibility with the preceding series.
6. Electrical Connections
6.1 General Description
All the Platinum® controllers may be fitted with a two wire (half duplex)
RS485 serial comm.s option. It makes the wiring simpler and enables a
larger connection length (maximum 1200 m).
The Platinum ® C10, M10, M300 and M400 instruments do not have any
line termination or polarisation system. If necessary a termination
resistance (120 ¼ W) must be connected to the terminals of the last
instrument of the line. In any case the polarisation is not possible.
The Platinum ® M5000, X100, X400 and X5000 instruments do have any
line termination or polarisation system. Please refere to the specific
chapter on these instruments.