32
22 23 Hold PV ( 0=Disabled 1=Enabled ) R/W
23 24 OP1 forced status by serial comm.s ( 0 = OFF 1 = On ) R/W
19
24 25 OP2 forced status by serial comm.s ( 0 = OFF 1 = On ) R/W
19
25 26 OP3 forced status by serial comm.s ( 0 = OFF 1 = On ) R/W
19
26 27 OP4 (logic) forced status by serial comm.s ( 0 = OFF 1 = On ) R/W
19
10.2 Read Status
Function 07 (Read Status) returns an eight bit status with the following
meanings:
Bit Address Variable
1 (LSB) 1 Local setpoint/Remote ( 0 = Local 1 = Remote )
2 2 Auto/Man ( 0 = Auto 1 = Man )
3 3 AL3 alarm status ( 0 = OFF, 1 = ON )
4 4 AL4 alarm status ( 0 = OFF, 1 = ON )
5 5 AL1 alarm status ( 0 = OFF, 1 = ON )
6 6 AL2 alarm status ( 0 = OFF, 1 = ON )
7 7 Out of range (0 = Normal operation, 1 = Safety)
8 (MSB) 8 Self Tuning ( 0=Disabled 1=Run )
10.3 Word zone - Page 1 Parameters
Address
Modbus JbuS Variable Parameter
Code
Type
0 1 PV Process variable
-
R
1 2 SP Setpoint
-
R
2 3 MV Main output
-
R/W
1
3 4 SPT Target setpoint
-
R/W
2
4 5 SPL Local setpoint
-
R/W
2
5 6 Proportional Band (Hysteresis ON - OFF)
P.b. (Hy)
R/W
6 7 Overshoot Control
O.C.
R/W
7 8 Integral time
t.i.
R/W
8 9 Derivative time
t.d.
R/W
9 10 Cycle time
t.c.
R/W
10 11 Low range
Sc.1o
R/W
11 12 High range
Sc.hi
R/W
12 13 AL1 alarm threshold
1***
R/W
13 14 AL2 alarm threshold
2***
R/W
14 15 AL3 alarm threshold
3***
R/W
15 16 AL4 alarm threshold
4***
R/W
16 17 AL1 alarm hysteresis Up
Hy1u
R/W
17 18 AL1 alarm hysteresis Down
Hy1d
R/W
18 19 AL2 alarm hysteresis Up
Hy2u
R/W
19 20 AL2 alarm hysteresis Down
Hy2d
R/W
20 21 AL3 alarm hysteresis Up
Hy3u
R/W
21 22 AL3 alarm hysteresis Down
Hy3d
R/W
22 23 AL4 alarm hysteresis Up
Hy4u
R/W
23 24 AL4 alarm hysteresis Down
Hy4d
R/W
24 25 Heat/cool proportional band
P.b. C
R/W
25 26 Heat/cool integral time
t.i. C
R/W
26 27 Heat/cool derivative time
t.d. C
R/W
27 28 Cool output cycling time
tc.C
R/W
28 29 Output minimum step
MU.tM
R/W
29 30 Setpoint low limit
SPLl.
R/W