31
14. To select the Timer action, a value between 0 and 7 must be
assigned as per the below table:
Timer action Serial value
Launch OP3 status Time
By Keypad OFF Second 0
By Keypad ON Second 1
Key + at power on OFF Second 2
Key + at power on ON Second 3
By Keypad OFF Minute 4
By Keypad ON Minute 5
Key + at power on OFF Minute 6
Key + at power on ON Minute 7
15. To select the digital input functions, a value between 0 and 4 must
be assigned as per the below table:
Digital input function Serial value
None 0
Keypad lock 1
Manual mode 2
Stand-by Setpoint 3
Timer launch 4
9.5 Termination and Polarization
The Platinum ® M400 instruments do not have any line termination or
polarization system. If necessary a termination resistance (120Ω ¼ W)
must be connected to the terminals of the last instrument of the line.
In any case the polarization is not possible.
10. M5000 Controller
10.1 Bit zone
Address
Modbus JbuS Variable Type
0 1 Remote status (0=LOC, 1=REM) R/W
1 2 Auto/Man ( 0 = Auto 1 = Man ) R/W
2 3 AL3 alarm status ( 0 = OFF, 1 = ON ) R
3 4 AL4 alarm status ( 0 = OFF, 1 = ON ) R
4 5 AL1 alarm status ( 0 = OFF, 1 = ON ) R
5 6 AL2 alarm status ( 0 = OFF, 1 = ON ) R
6 7 Out of range (0 = Normal operation, 1 = Safety) R
7 8 Self Tuning ( 0=Disabled 1=Run ) R
8 9 - R
9 10 Out of range (0 = Normal operation, 1 = Safety) R
10 11 - -
11 12 - -
12 13 1
st
Stored setpoint R/W
13 14 2
nd
Stored setpoint R/W
14 15 - -
15 16 - -
16 17 IL1 Digital input status (0 = OFF, 1 = ON) R
17 18 IL2 Digital input status (0 = OFF, 1 = ON) R
18 19 - -
19 20 - -
20 21 Keys enable ( 0=Enabled 1=Disabled ) R/W
21 22 Slope enable ( 0=Disabled 1=Enabled ) R/W