19
Rt
Rt
Co mmon
Rg
G/R
Rg
G/R
Rg
G/R
Rg
G/R
Supervisor
Device 1 Device 2 Device "n"
G = Transmitter
R = Receiver
G/R = Bi-directional (Receiver/Transmitter) buffer
Rt = Termination resistance: the transmitter can drives up to 32
receivers plus two 120 resistors.
Rg = 100 Resistor
From the above drawing it may be seen that a “star” connection is not
valid. Each branch would have to be terminated, which in turn would
reduce the overall the impedance of the line. In these conditions, the
signal level would be too low for reliable communications.
6.3.1 References
GOULD Gould Modbus Protocol Reference Guide
(PI-MBUS-300 Rev. B)
APRIL JbuS Specification
GLOBAL ENG. DOC. EIA STANDARD RS -485
7. C10 / M10 Controllers
7.1 Bit Zone
Address
Modbus JbuS Variable Type
0 1 - -
1 2 - -
2 3 - -
3 4 Main output condition (0 = OFF, 1 = ON) R
4 5 AL2 alarm status (0 = OFF, 1 = ON) R
5 6 AL3 alarm status (0 = OFF, 1 = ON) R
6 7 Out of range (0 = Normal operation, 1 = Safety) R
7 8 Auto-Tune (0 = OFF, 1 = Run) R
8 9 - -
9 10 Out of range (0 = Normal operation, 1 = Safety) R
10 11 - -
11 12 - -
12 13 - -
13 14 - -
14 15 - -
15 16 - -