111 112 CT primary high range
Ht.F.S
R/W
112 113 Password
Code
R/W
113 114 Retransm. calibration low range (for Athena
Controls only)
CAL.3
R/W
114 115 Retransm. calibration high range (for Athena
Controls only)
CAL.4
R/W
115 116 Timer setting
t.Mod
R/W
17
116 117 Timer action
t.Act
R/W
18
117 118 IL1 digital input function
IL1
R/W
19
118 119 IL2 digital input function
IL2
R/W
19
119 120 IL3 digital input function
IL3
R/W
19
Address
Modbus JbuS Variable Parameter
code
Type
120 121 Manufacturer code (600 for Athena Controls) R(W)
6
121 122 Product code (“X1” or X3”)
note X3=X400 product R
122 123 R
123 124 Release code (p. es. “ 00A”)
7
R
124 125 R
125 126 Custom code R
126 127 - - -
127 128 - - -
Notes:
1. Assignment of Setpoint to the addresses JbuS 2 and 4 writes the
Computer Setpoint. It is different from the Local Setpoint, which can
be in any case set by keypad.
2. Assignment of output at the address JbuS 3 is only possible if the the
Auto/Man option if fitted and when the controller is in Manual mode.
3. Assignment of Setpoint to the address JbuS 5 writes the Local
Setpoint (the previous value is lost).
4. In case of ON - OFF output (address JbuS 6) the proportional band
is substituted by the output hysteresis.
5. All the configuration parameters are accepted, if valid, but not
brought into effect. To execute the reconfiguration procedure and
bring the changes into effect, the code 55AAh must be written at the
address JbuS 121.
6. Address JbuS 121 is read only, but if the code 55AAh (21930d) is
written at this address, the configuration is brought into effect.
7. The JbuS 122 + 123 and 124 + 125 addresses contain the strings (of
4 characters) for the product and release codes: each address
represents two characters, the most significant byte in the word
contains the ASCII code of the second.
8. To select the program status, the value between 0 and 4 must be
assigned as per the below table:
Program status Serial value
Reset 0
Hold 1
Run 2
Hold / Back (note) 3
Program end 4
Note: If the PV controlled input value exceeds the band, the
controller switches automatically to this mode.