12.6 RS-485 Configuration Dip Switch
On the RS485 board a 4 position dip Switch is provided. It enables the
correct hardware configuration of the instrument serial comm.s port as
follows:
Position On OFF
1 Polarisation +5Vcc Polarisation excluded
2 Termination set Termination excluded
3 Polarisation 0 Vcc Polarisation excluded
4 - -
13. Configuration software for Platinum controllers
The configuration software APG2SW4 can be used with all the Platinum
instruments: C10, M10, M300, M400, M5000, X100, X400 and X5000,
even those without the RS 485 communications option.
Instruments C10, M10, M300 and M400 without
the RS 485
communications option can be configured using this software, but the
special cable APG2SCI, (available separately), will be required to
interface between the computer port and the instrument.
For instruments C10, M10, M300 and M400 without
the RS 485
communications option, connect the special cable APG2SCI to a spare
port on the computer and the crimp connectors to terminals 10 – brown
and 11 – black on the instrument. The computer and the instrument
should be turned off during this procedure.
For instruments C10, M10, M300 and M400, terminals 10 and 11 are
also the SSR drive voltage output. To avoid a communication error, open
circuit the sensor input terminals, to prevent the SSR drive output from
turning on. Also, for previously configured instruments, ensure that the
configuration code, ‘ConF’ ends in a ‘0’ e.g. 2000
, i.e. Alarm 2 is turned
off and that the SSR drive voltage output is not used as main output.